Thermocouples for temperature measurement up to 1,700 °C

Thermocouples generate a voltage directly dependent on temperature. They are particularly suited for high temperatures up to 1,700 °C. Instrument designs from mineral-insulated sheathed cable are very resistant against extremely high vibration loads (depending on instrument model, sensor element and wetted materials). For thermocouples, the accuracy classes 1 and 2 apply (standard and special). They are available with a tolerance value in accordance with IEC 60581 / ASTM E230.

Sales contact

WIKA Instruments Namibia (Pty.) Ltd.

Tel.:
+26 4 61238811
Fax.:
+26 4 61233403
sales@wika.com.na

FAQ

What measures should be taken with the installation of high-temperature probes with ceramic thermowells?

Installation and removal should be carried out slowly and gradually, in order to prevent the ceramic thermowell being destroyed by internal thermal stresses.  This must be either preheated or slowly inserted, e.g. 1 ... 2 cm / min for temperatures to 1,600 &de ... More

What is the permissible minimum bending radius for an MI cable?

VDI/VDE 3511 Sheet 2 recommends a radius of curvature R of ≥ 5 x D (D=external diameter of the MI cable), some manufacturers of MI cable even give ≥ 3 x D as the minimum bending radius.